Warranty Period | 5-year (Refer to Instruction Manuals) |
---|
Please refer to derating curve, because the rated load current depends on cooling method that is convection cooling or forced air.
*Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations.
Features of ADA1000F-30
• High power & peak power• Power up with fan (optional)
• Parallel operation/master-slave operation/N+1 redundant(optional)
• Harmonic attenuator (Complies with IEC61000-3-2)
• Universal input voltage (AC85 - 264V)
• Optional:remote ON/OFF, alarms
• Current monitor
• DIN rail (35mm) optional
Ordering Information and Options
ADA(1) 1000(2) F(3) - 24(4) - □(5)
(1) Series name(2) Output wattage
(3) Universal input
(4) Output voltage
(5) Optional
G: Low leakage current
E: Low leakage current
and EMI class A
F: with Fan unit
T: Vertical terminal block
J: Connector type
C: with Coating
R: Remote ON/OFF
N1: DIN rail
W: Alarms and Redundant
operation
Specification is changed at option, refer to Instruction Manual.
Optional Parts
Attachment Plate、Harness、Fan unitRecommended EMI Filters
Specification
Contents | Specifications | |
---|---|---|
Input Voltage | AC85 - 264V 1Φ or DC120 - 350V (AC64 or DC90 optionally available) * | |
Output | Wattage |
495W (Peak: 1500W) ACIN 100V Convection Cooling 780W (Peak: 1500W) ACIN 100V Forced Air Cooling 600W (Peak: 1980W) ACIN 200V Convection Cooling 1005W (Peak: 1980W) ACIN 200V Forced Air Cooling |
Voltage/Current |
30V 16.5A (Peak :50A) ACIN 100V Convection Cooling 30V 26A (Peak :50A) ACIN 100V Forced Air Cooling 30V 20A (Peak :66A) ACIN 200V Convection Cooling 30V 33.5A (Peak :66A) ACIN 200V Forced Air Cooling |
|
Adjustable Voltage Range | 27.0 - 33.0V | |
Protection Circuit And Others | Overcurrent Protection | Works over 101% of peak current and recovers automatically |
Overvoltage Protection | 40 - 48V | |
Remote ON/OFF | Requirement for external source (Option: -R, refer to Instruction Manual 5) | |
Remote Sensing | - | |
Others | - | |
Operating Temperature/Humidity | -10 to +71℃, 20 - 90%RH (Non condensing) (Refer to DERATING CURVE) | |
Safety And Noise Regulations | Agency Approvals (At only AC input) | UL60950-1, C-UL (CSA60950-1) , EN60950-1, EN60065, EN50178 Complies with DEN-AN and IEC60950-1 (At only AC input) |
Conducted Noise | Complies with FCC-B, CISPR22-B, EN55022-B, VCCI-B | |
High Attenuation | Complies with IEC61000-3-2 * | |
Others | Dimensions (WxHxD) | 75x127x280mm [2.95x5x11.02 inches] (without terminal block) |
Weight | 2.5kg max | |
Cooling Method | Convection/Forced air | |
Warranty Period | 5-year (Refer to Instruction Manuals) |