Three-phase 500VAC 50A
Compact and low profile
High-attenuation from 150kHz to 1MHz
1-stage filter
Compact and low profile
High-attenuation from 150kHz to 1MHz
1-stage filter





Warranty Period | 5-year |
---|
Features of JAC-50
Maximum input voltage 528VAC: 10% fluctuations in voltage 480VACSelectable leakage current value
Ordering Information and Options
JAC(1) - 50(2) - 683(3) - □(4)
(1) Model Name(2) Rated Current
(3) Line to ground capacitor code
Refer to Product Line-up.
* When the line to ground capacitor code is different, the attenuation characteristic is
different.
(4) Options
H:Ultra high-attenuation type
"103" , "223" , "683" is applied.
U:lmprove differential mode attenuation (Rated voltage 250V)
Product Line-up
Product Name | Leakage Current* | Line to ground capacitor (nominal value) |
---|---|---|
JAC-50-103 |
0.5 mA / 1.0mA max 0.05mA / 0.1mA max |
0.01μF |
JAC-50-223 |
1.0mA / 2.0mA max 0.1mA / 0.2mA max |
0.022μF |
JAC-50-683 |
2.5 mA / 5.0mA max 0.35mA / 0.7mA max |
0.068μF |
JAC-50-224 |
15 mA / 24 mA max 2.0mA / 4.0mA max |
0.22μF |
JAC-50-155 |
80 mA / 125mA max 9.0mA / 18 mA max |
1.5μF |
- * Input 250/500VAC 60Hz ( input Δ-connection 250/400VAC 60Hz in case of 224,155)
Upper row: Δ-connection, Lower row: Y-connection
- Catalog (Including Dimensions)
- Instruction Manuals (Including attenuation characteristics)
- Technical Notes
Specification
Contents | Specifications | |
---|---|---|
Rated Voltage | Three-phase Three-wire 500V 50/60Hz | |
Rated Current | 50A | |
Operating Temperature | -40 to +85℃ (Refer to Derating Curve) | |
Agency Approvals |
UL60939[Overvoltage Category:Ⅲ Altitude:3000m] CSA C22.2 No.8(C-UL) EN60939(DEMKO)[Overvoltage Category:Ⅲ Altitude:3000m] ENEC |
|
Others | Dimensions (WxHxD) | 65x54x153 mm [2.56x2.13x6.02 inches] |
Weight | 800g max | |
Warranty Period | 5-year |
- * For further information and how to use, please see in Cosel product catalog.
Circuit Diagram
Derating Curve
Documents Download
Technical Data | ||
---|---|---|
CAD Data | DXF | |
3D CAD Data | STEP | |
IGES |
- * For another documents aren't listed, please feel free to contact to a Cosel representative.
Similar Model (Rated Voltage and Current)
Features | Model Name | Released | Catalog Instruction Manuals |
|
---|---|---|---|---|
![]() |
General purpose, Low profile, High-attenuation type, 1-stage filter |
TAC-50 | 2008 |
Catalog Instruction Manuals |
![]() |
Low profile, Ultra high-attenuation type, 1-stage filter |
TAH-50 | 2016 |
Catalog Instruction Manuals |
![]() |
General-purpose, Book type, High-attenuation, 1-stage filter |
FTA-50 | 2013 |
Catalog Instruction Manuals |
![]() |
Low-profile, High-attenuation, 2-stage filter |
TBC-50 | 2008 |
Catalog Instruction Manuals |
![]() |
Book type, EMI/EMC Filter for motor drive system, 2-stage filter |
FSB-50 | 2018 |
Catalog Instruction Manuals |