Three-Phase Four-Wire System 500VAC 64A
High-Attenuation from 150kHz to 1MHz
1-Stage Filter
High-Attenuation from 150kHz to 1MHz
1-Stage Filter
Warranty Period | 5-year |
---|
Features of YAC-64
Three-Phase Four-Wire System EMI/EMC Filter ideal for High-power office equipment and Energy storage systemsSuitable for 150kHz to 1MHz conduction noise reduction
Product lineup that can flexibly respond to system and capacity changes in a compact/same body size
Ordering Information and Options
YAC(1) - 64(2) - 685(3)
(1) Model Name(2) Rated Current
(3) Line to Ground Capacitor Code
Refer to Product Line-up.
Product Line-up
Product Name | Leakage Current* | Line to ground capacitor (nominal value) |
---|---|---|
YAC-64-685 |
10.7mA typ *1 55mA max *2 |
6.8μF |
*Y-Connection
*1 At normal operation (Input 500V 50Hz)with applying 10V between N (N') and FG (According to IEC60939) .
*2 At the worst case under normal operation (Input 500V 60Hz) .
- Catalog (Including Dimensions)
- Instruction Manuals (Including attenuation characteristics)
- Technical Notes
Specification
Contents | Specifications | |
---|---|---|
Rated Voltage | Three-Phase Four-Wire System Y-Connection 500/289VAC 50/60Hz | |
Rated Current | 64A | |
Operating Temperature | -40 to +85℃ (Refer to Derating Curve) | |
Agency Approvals |
UL60939[Overvoltage Category:Ⅲ Altitude:3000m] CSA C22.2 No.8(C-UL) EN60939(DEMKO)[Overvoltage Category:Ⅲ Altitude:3000m] ENEC |
|
Others | Dimensions (WxHxD) | 100x88x179 mm [3.94x3.46x7.05 inches] |
Weight | 1.7kg max | |
Warranty Period | 5-year |