TSD-400

Released 2021
Three-Phase 500VAC 400A Low-Profile
Ultra High-Attenuation Type for Motor Drive System(Multi-Functional Regenerative Converter)
Improve Saturation Resistance
Multi-Stage Filter
 
RoHS ECO MODEL
UL・C-UL DEMKO ENEC
Warranty Period 5-year

Features of TSD-400

Input and Output Terminals : Busbar Type
Maximum Input Voltage 528VAC: 10% Fluctuations in Voltage 480VAC
Selectable Leakage Current Value

Ordering Information and Options

TSD(1)  -  400(2)  -  186(3)  


(1) Model Name
(2) Rated Current
(3) Line to ground capacitor code
  Refer to Product Line-up.
  * When the line to ground capacitor code is different, the attenuation characteristic is
different.
  * Please contact us about low leakage current type (Change to low grounding
    capacitor).

Product Line-up

Product Name Leakage Current* Line to ground capacitor
(nominal value)
TSD-400-105 45mA / 70mA max
3.5mA / 7.0mA max
CY1:0.22μF
CY2:0.1μF
CY3:0.22μF
TSD-400-215 80mA / 130mA max
7.5mA / 15mA max
CY1:1.0μF
CY2:0.1μF
CY3:1.0μF
TSD-400-665 220mA / 350mA max
20mA / 40mA max
CY1:2.2μF
CY2:2.2μF
CY3:2.2μF
TSD-400-136 420mA / 660mA max
40mA / 80mA max
CY1:2.2μF
CY2:2.2μF
CY3:2.2μF
TSD-400-186 540mA / 850mA max
50mA / 100mA max
CY1:2.2μF
CY2:2.2μF
CY3:2.2μF
  •   * Input Δ-connection 250/400VAC 60Hz
     Input Y-connection 250/500VAC 60Hz
      Upper row: Δ-connection, Lower row: Y-connection

Specification

Contents Specifications
Rated Voltage Three-Phase Three-Wire 500V 50/60Hz
Rated Current 400A
Operating Temperature -40 to +85℃ (Refer to Derating Curve)
Agency Approvals UL60939[Overvoltage Category:Ⅲ Altitude:3000m]
CSA C22.2 No.8(C-UL)
EN60939(DEMKO)[Overvoltage Category:Ⅲ Altitude:3000m]
ENEC
Others Dimensions (WxHxD) 210x125x360 mm [8.27x4.92x14.17 inches]
Weight 10.0kg max
Warranty Period 5-year
  • * For further information and how to use, please see in Cosel product catalog.

Circuit Diagram

Derating Curve

Documents Download

Technical Data
CAD Data DXF
3D CAD Data STEP
IGES
  • * For another documents aren't listed, please feel free to contact to a Cosel representative.

Similar Model (Rated Voltage and Current)

Features Model Name Released Catalog
Instruction Manuals
Low-profile,
Ultra high-attenuation type of common mode noise from 150kHz to 1MHz
Multi-stage filter
TSC-400 2013 Catalog
Instruction Manuals
  • * For further information and how to use, please see in Cosel product catalog.
Table1 Product Status Information
No. Product Status Definition
1 New Product New Product. Recommended for new design.
2 Recommended Recommended for new design.
3 blank Product in mass production
4 NRND Not recommended for new design.
5 To be discontinued PDN (Product Discontinuation Notice) is issued and LTB (Last Time Buy) is under consideration.
6 Discontinued LTB order is no longer available.