TSC-400

Released 2013
Three-phase 500VAC 400A Low-profile
Ultra high-attenuation type of common mode noise from 150kHz to 1MHz
Multi-stage filter
 
RoHS ECO MODEL
UL・C-UL VDE ENEC
Warranty Period 5-year

Features of TSC-400

Input and output terminals : Busbar type
Maximum input voltage 528VAC: 10% fluctuations in voltage 480VAC
Selectable leakage current value

Ordering Information and Options

TSC(1)  -  400(2)  -  665(3) - (4) 


(1) Model Name
(2) Rated Current
(3) Line to ground capacitor code
  Refer to Product Line-up.
  * When the line to ground capacitor code is different, the attenuation characteristic is
different.
  * Please contact us about low leakage current type (Change to low grounding
    capacitor).
(4) Option
H:Ultra high-attenuation type

Product Line-up

Product Name Leakage Current* Line to ground capacitor
(nominal value)
TSC-400-000 50μA /  80μA  max 
50μA / 100μA max
CY1:Not Provided
CY2:Not Provided
CY3:Not Provided
TSC-400-304 10.5mA / 21.0mA max
1.5mA / 3.0mA max
CY1:0.1μF
CY2:0.1μF
CY3:0.1μF
TSC-400-664 23mA / 46mA max
3.5mA / 7.0mA max
CY1:0.22μF
CY2:0.22μF
CY3:0.22μF
TSC-400-665 220mA / 350mA max
20mA / 40mA max
CY1:2.2μF
CY2:2.2μF
CY3:2.2μF
  •   * Input 250/500VAC 60Hz ( input Δ-connection 250/400VAC 60Hz in case of 665)
      Upper row: Δ-connection, Lower row: Y-connection

Specification

Contents Specifications
Rated Voltage Three-phase Three-wire 500V 50/60Hz
Rated Current 400A
Operating Temperature -40 to +85℃ (Refer to Derating Curve)
Agency Approvals UL1283, CSA C22.2 No.8 (C-UL) , DIN EN60939 VDE0565 Teil3-1, ENEC
Others Dimensions (WxHxD) 210x100x360 mm [8.27x3.94x14.17 inches]
Weight 9.5kg max
Warranty Period 5-year
  • * For further information and how to use, please see in Cosel product catalog.

Circuit Diagram

Derating Curve

Documents Download

Technical Data
CAD Data DXF
3D CAD Data STEP
IGES
  • * For another documents aren't listed, please feel free to contact to a Cosel representative.
Table1 Product Status Information
No. Product Status Definition
1 New Product New Product. Recommended for new design.
2 Recommended Recommended for new design.
3 blank Product in mass production
4 NRND Not recommended for new design.
5 To be discontinued PDN (Product Discontinuation Notice) is issued and LTB (Last Time Buy) is under consideration.
6 Discontinued LTB order is no longer available.