Warranty Period | 3-year |
---|
*Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations.
Features of SCDA10000T-48
• High power, AC-DC front end power supply• Three-phase input (AC160 - 264V 3Φ)
• High efficiency (90%) , High power factor (0.99)
• Harmonic attenuator (Complies with IEC61000-3-12)
• Complies with SEMI F47
• Wide output voltage adjustable range approximately 0 to 52.8V (Optional)
• Constant current regulation provided with additional external components (Optional)
• Parallel operation and Parallel redundancy operation (SCHA10000T)
• System ON/OFF (Remote ON/OFF)
• Alarms
• Output Voltage Monitor
• Parallel Control (Start in/out)
• Remote Signal ON/OFF
Ordering Information and Options
SC(1) H(2) A(3) 10000(4) T(5) - 48(6) - □(7)
(1) Series name(2) External form
H: Wide front interface
D: Compact front interface
(3) Single output
(4) Output wattage
(5) Three-phase input
(6) Output voltage
(7) Optional
Optional Parts
Harness,Fan unitRecommended EMI Filters
Specification
Contents | Specifications | |
---|---|---|
Input Voltage | AC160 - 264V 3Φ | |
Output | Wattage | 9984W |
Voltage/Current | 48V 208A | |
Adjustable Voltage Range | 43.2 - 52.8V | |
Protection Circuit And Others | Overcurrent Protection | Activate over 105% - 120% of rated current and recovers autmatically. (Shut down if low-voltage protection activated) |
Overvoltage Protection | 56.0 - 59.0V (shut down) | |
Remote ON/OFF | Provided | |
Remote Sensing | - | |
Others | - | |
Operating Temperature/Humidity | 0 to +50℃, 20 - 85%RH (Non condensing) | |
Safety And Noise Regulations | Agency Approvals (At only AC input) | UL60950-1, C-UL (CSA60950-1) , EN60950-1complies |
Conducted Noise | Complies with EN55011 Group1-A, EN55022-A, CISPR22-A, FCC part15 classA, additional EMI/EMC Filter required for meeting class B | |
High Attenuation | Complies with IEC61000-3-12 | |
Others | Dimensions (WxHxD) | 310.5x150x510mm [12.22x5.91x20.08 inches] |
Weight | 20kg max | |
Cooling Method | Forced cooling (require external fan) | |
Warranty Period | 3-year |
- * For further information and how to use, please see in Cosel product catalog.
Block Diagram
Documents Download
Technical Data | ||
---|---|---|
CAD Data | DXF | |
3D CAD Data | STEP | |
IGES |
- * For another documents aren't listed, please feel free to contact to a Cosel representative.