Rated Input: AC170 - 264V 3Φ
Rated Output Wattage: 10000W
Rated Output Voltage: 48V
Rated Output Wattage: 10000W
Rated Output Voltage: 48V
Warranty Period | 3-year |
---|
*Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations.
Recommended Model for Replacement
Type | Model Name | Released | Catalog Instruction Manuals Documents for replacement |
|
---|---|---|---|---|
Enclosed type | FETA7000T | 2017 |
|
- * For further information and how to use, please see in Cosel product catalog.
Features of SCDA10000T
• High power, AC-DC front end power supply• Three-phase input (AC160 - 264V 3Φ)
• High efficiency (90%) , High power factor (0.99)
• Harmonic attenuator (Complies with IEC61000-3-12)
• Complies with SEMI F47
• Wide output voltage adjustable range approximately 0 to 52.8V (Optional)
• Constant current regulation provided with additional external components (Optional)
• Parallel operation and Parallel redundancy operation (SCHA10000T)
• System ON/OFF (Remote ON/OFF)
• Alarms
• Output Voltage Monitor
• Parallel Control (Start in/out)
• Remote Signal ON/OFF
Ordering Information and Options
SC(1) H(2) A(3) 10000(4) T(5) - 48(6) - □(7)
(1) Series name(2) External form
H: Wide front interface
D: Compact front interface
(3) Single output
(4) Output wattage
(5) Three-phase input
(6) Output voltage
(7) Optional
Recommended EMI Filters
Product Line-up
Product Name | Output Wattage | Output Voltage・Current |
---|---|---|
SCDA10000T-48 | 9984W | 48V 208A |
- * For further information and how to use, please see in Cosel product catalog.
Block Diagram
Optional Parts
Harness,Fan unit
Category | Part Number | Description | DXF | |
---|---|---|---|---|
Attachment |
F-SCD-1 | Attachment for mounting to 19-inch rack. (bracket type) | ||
F-SCD-2 | Attachment for mounting to 19-inch rack. | |||
Harness |
H-OU-35 | Mating harness for output. | - | |
H-PA-7 | Harness for using parallel connection. (SLAVE unit - SLAVE unit) | - | ||
H-PA-8 | Harness for using parallel connection. (MASTER unit - SLAVE unit) | - | ||
H-SN-27 | Harness for using remote signal ON/OFF function. | - | ||
H-SN-28 | Harness for using MAS,SLV,CTB,PCONT,COM terminal. | - | ||
H-SN-29 | Harness for using system ON/OFF function. | - | ||
H-SN-30 | Harness for using alarm / output voltage monitor terminal. | - | ||
H-SN-35 | Harness for using AUX(5V) remote control and PG terminal. | - | ||
Fan unit |
FAN-SCD-1 | Fan unit for SCDA10000T-48. | - | |
FAN-SCD-2 | Fan unit for SCDA10000T-48. | - |