Warranty Period | 5-year (Refer to Instruction Manuals) |
---|
*Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations.
Features of PBA1500T-24
• Super small-size & light weight• Harmonic attenuator (Complies with IEC61000-3-2): except PBA1500T
• Universal input (AC85 - 264V): PBA1500T AC170-264V 3Φ
• Efficiency increased with synchronous rectification technology (PBA50F - 150F)
• Variety of option (PBA10F - 150F, PBW15F - 50F)
• Parallel operation and Parallel redundancy operation (PBA300F - 1500F, PBA1500T)
• Fan alarm, Remote ON/OFF and other functions (PBA300F - 1500F, PBA1500T)
Ordering Information and Options
PB(1) A(2) 1500(3) T(4) - 5(5) - □(6)
(1) Series name(2) Single output
(3) Output wattage
(4) Universal input
(5) Output voltage
(6) Optional
C: with Coating
G: Low leakage current
U: Operation stop voltage is set at a lower value
F1: With Long-Life fan
F3: Reverse air exhaust type
F4: Low speed fan
Refer to instruction manual 7.1.
Recommended EMI Filters
Specification
Contents | Specifications | |
---|---|---|
Input Voltage | AC170 - 264V 3Φ * | |
Output | Wattage | 1680W |
Voltage/Current | 24V 70A (105) A | |
Adjustable Voltage Range | 16.50 - 26.40V | |
Protection Circuit And Others | Overcurrent Protection | Works over 105% of rated current or 101% of peak current and recovers automatically |
Overvoltage Protection | Vo+4.8 - 9.6V | |
Remote ON/OFF | Provided | |
Remote Sensing | Provided | |
Others | - | |
Operating Temperature/Humidity | -20 to +71℃ (Required Derating) , 20 - 90%RH (Non condensing) | |
Safety And Noise Regulations | Agency Approvals (At only AC input) |
UL60950-1, C-UL (CSA60950-1) , EN62368-1 Complies with DEN-AN |
Conducted Noise | Complies with FCC Part15 classB, VCCI-B, CISPR22-B, EN55011-B, EN55022-B, additional EMI/EMC Filter required for meeting class B | |
High Attenuation | - | |
Others | Dimensions (WxHxD) | 178x61x268mm [7.01x2.4x10.55 inches] (without terminal block and screw) |
Weight | 3.4kg max | |
Cooling Method | Forced cooling (internal fan) | |
Warranty Period | 5-year (Refer to Instruction Manuals) |
- * For further information and how to use, please see in Cosel product catalog.
Block Diagram
Documents Download
Technical Data | ||
---|---|---|
CAD Data | DXF |
- * For another documents aren't listed, please feel free to contact to a Cosel representative.
Optional Parts
Harness, Insulated tube
Category | Part Number | Description | DXF | |
---|---|---|---|---|
Harness |
H-PA-3 | Harness for parallel operation. | - | |
H-SN-20 | Harness for using all functions of CN1 and CN2. | - | ||
H-SN-21 | Harness for using all functions except remote sensing of CN2. | - | ||
H-SN-22 | Harness for using all functions of CN3. | - | ||
H-SN-24 | Harness for using example remote ON/OFF circuit C. | - | ||
Fan unit |
FAN-PB15 | Fan unit for PBA1500F. (Standard model) |
- | |
FAN-PB15-F1 | Fan unit for PBA1500F. (F1 option : Long life fan) |
- | ||
FAN-PB15-F3 | Fan unit for PBA1500F. (F3 option : Reversed air flow) |
- | ||
FAN-PB15-F4 | Fan unit for PBA1500F. (F4 option : Lower speed fan) |
- | ||
Insulated tube |
T-PBA1500-1 | Insulation tube for output terminal base. | - | |
T-PBA1500-2 | Insulation tube for output terminal base. | - |