Three-Phase 500VAC 800A Low-Profile
Ultra High-Attenuation Type for Motor Drive System(Multi-Functional Regenerative Converter)
Improve Saturation Resistance
Multi-Stage Filter
Ultra High-Attenuation Type for Motor Drive System(Multi-Functional Regenerative Converter)
Improve Saturation Resistance
Multi-Stage Filter
Warranty Period | 5-year |
---|
Features of TSD-800
Input and Output Terminals : Busbar TypeMaximum Input Voltage 528VAC: 10% Fluctuations in Voltage 480VAC
Selectable Leakage Current Value
Ordering Information and Options
TSD(1) - 800(2) - 356(3)
(1) Model Name
(2) Rated Current
(3) Line to Ground Capacitor Code
Refer to Product Line-up.
* When the line to ground capacitor code is different, the attenuation characteristic is
different.
* Please contact us about low leakage current type (Change to low grounding
capacitor).
Product Line-up
Product Name | Leakage Current* | Line to ground capacitor (nominal value) |
---|---|---|
TSD-800-000 *1 |
50µA / 100µA max 50µA / 100µA max |
CY1:なし CY2:なし CY3:なし |
TSD-800-304 *1 |
10.5mA / 21.0mA max 1.5mA / 3.0mA max |
CY1:0.1μF× 1 CY2:0.1μF× 1 CY3:0.1μF× 1 |
TSD-800-664 *1 |
23mA / 46mA max 3.5mA / 7.0mA max |
CY1:0.22μF× 1 CY2:0.22μF× 1 CY3:0.22μF× 1 |
TSD-800-316 *2 |
960mA / 1500mA max 90mA / 180mA max |
CY1:2.2μF× 2 CY2:2.2μF× 2 CY3:2.2μF×10 |
TSD-800-356 *2 |
1080mA / 1700mA max 100mA / 200mA max |
CY1:2.2μF× 4 CY2:2.2μF× 4 CY3:2.2μF× 8 |
TSD-800-446 *2 |
1300mA / 2100mA max 110mA / 220mA max |
CY1:2.2μF× 5 CY2:2.2μF× 5 CY3:2.2μF×10 |
* Upper row: Δ-Connection, Lower row: Y-Connection
*1 Input Δ-Connection 250/500VAC 60Hz Input Y-Connection 250/500VAC 60Hz
*2 Input Δ-Connection 250/400VAC 60Hz Input Y-Connection 250/500VAC 60Hz
- Catalog (Including Dimensions)
- Instruction Manuals (Including attenuation characteristics)
- Technical Notes
Specification
Contents | Specifications | |
---|---|---|
Rated Voltage | Three-Phase Three-Wire 500VAC 50/60Hz | |
Rated Current | 800A | |
Operating Temperature | -40 to +85℃ (Refer to Derating Curve) | |
Agency Approvals |
UL60939[Overvoltage Category:Ⅲ Altitude:3000m] CSA C22.2 No.8(C-UL) EN60939(DEMKO)[Overvoltage Category:Ⅲ Altitude:3000m] ENEC |
|
Others | Dimensions (WxHxD) | 190x155x346 mm [7.48x6.10x13.62 inches] |
Weight | 11.5kg max | |
Warranty Period | 5-year |
- * For further information and how to use, please see in Cosel product catalog.
Circuit Diagram
Derating Curve
Documents Download
Technical Data | ||
---|---|---|
CAD Data | DXF | |
3D CAD Data | STEP | |
IGES |
- * For another documents aren't listed, please feel free to contact to a Cosel representative.