PCA600F-5

Released 2018

Features of PCA600F-5

• Low profile (41mm, 1.61inch = meet 1U height)
• DC input 88 - 370VDC possible
• Output derating required (85V - 90VAC/88V - 110VDC)
• For medical electric equipment
(ANSI/AAMI ES60601-1, EN60601-1 3rd, IEC60601-1-2 4th Ed.)
• Medical Isolation Grade 2MOPP
• With AUX output 12V 0.1A (Voltage variable range 5 - 12V)
• Constant current function
• Output voltage can be adjusted to near 0V
• With various alarms
• Parallel Operation / N+1 Parallel Redundancy Operation possible
• Monitoring function and various setting values can be changed by communication
• Complies with SEMI F-47(Io:100%max at ACIN 200V, 70%max at ACIN 100V)
• Meets UL508 (Option: -T5)

Ordering Information and Options

PC(1)  A(2)  600(3)  F(4) - (5)  -  (6)  


(1) Series name
(2) Single output
(3) Output wattage
(4) Universal input
(5) Output voltage
(6) Optional
  C: with Coating
  G: Low leakage current
  T: Terminal Block Style
    (Only 12V,15V,24V,32V and 48V)
  I: with PMBus interface
  F2: Reverse air exhaust type
  P3: Master-slave Operation
  W1: Alarm function
  T5: UL508
    (Only 12V,15V,24V,32V and 48V)
For option details, refer to instruction manual 6.1.
3D product images are available.

Read Me First
Standard model (Bus bar)   T: Terminal Block Style (Only 12V,15V,24V,32V and 48V)

Recommended EMI Filters

Specification

Contents Specifications
Input Voltage 85 - 264VAC 1Φ *
Output Wattage 600W
Voltage/Current 5V 120A
Adjustable  Voltage Range 3.00 - 6.00V
Protection Circuit And Others Overcurrent Protection Works over 105% of rated current and recovers automatically
Overvoltage Protection 6.25 - 7.00V
Remote ON/OFF Provided
Remote Sensing Provided
Others -
Operating Temperature/Humidity -20 to +70℃ (Required Derating) , 20 - 90%RH (Non condensing)*
Safety And Noise Regulations Agency Approvals (At only AC input) UL62368-1, C-UL(CSA62368-1),EN62368-1, ANSI/AAMI ES60601-1, EN60601-1 3rd*
Conducted Noise Complies with FCC Part15 classB, VCCI-B, CISPR32-B, EN55011-B, EN55032-B
High Attenuation Complies with IEC61000-3-2 *
Others Dimensions (WxHxD) 89×41×152mm [3.50x1.61x5.98 inches] (without terminal block and screw)
Weight 840g max
Cooling Method Forced cooling (internal fan)
Warranty Period 5-year (Refer to Instruction Manuals)
  • * For further information and how to use, please see in Cosel product catalog.

Block Diagram

Documents Download

Technical Data
CAD Data DXF
3D CAD Data STEP
IGES
  • * For another documents aren't listed, please feel free to contact to a Cosel representative.

Optional Parts

Category Part Number Description PDF DXF
Harness
H-PA-14 Harness for serial operation. -
H-PA-15 Harness for parallel operation and N+1 parallel redundancy operation. -
H-PA-16 Harness for parallel operation of mater-slave. -
H-SN-48 Harness for using all functions of CN1 and CN2. -
H-SN-49 Harness for using all functions except remote sensing of CN1 and CN2. -
H-SN-50 Harness for using all functions of CN3. -
H-SN-51 Harness for using all functions of CN4. -
H-SN-52 Harness for using example remote ON/OFF circuit C. -
H-SN-53 Harness for using in slave setting of mater-slave operation. -
H-SN-54 Harness for using in effective setting of external output voltage adjustment. -
H-SN-66 Harness for using PMBus communication(for -I option). -
Communication converter
CR-PC-1 This is a unit to convert Extended UART signal to RS232 signal mutually. -
CR-PC-2 This is a unit to convert Extended UART signal to RS485(Modbus-RTU) signal mutually. -
Table1 Product Status Information
No. Product Status Definition
1 New Product New Product. Recommended for new design.
2 Recommended Recommended for new design.
3 blank Product in mass production
4 NRND Not recommended for new design.
5 To be discontinued PDN (Product Discontinuation Notice) is issued and LTB (Last Time Buy) is under consideration.
6 Discontinued LTB order is no longer available.