KLNA120F-48

Released 2015
RoHS ECO MODEL
UL・C-UL DEMKO CE
Warranty Period 5-year (Refer to Instruction Manuals)

*Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations.

Features of KLNA120F-48

• For DIN (35mm) rail products
• Wide operating ambient temperature range
• I/O terminal has 2 types, Euro Style and Barrier Blocks Style
• Built in overcurrent protection, overvoltage protection circuits

Ordering Information and Options

KL(1)  A(2)  120(3)  F(4)  -  (5)  -  (6)  

(1) Series name
KHE: Euro style I/O terminals
KHN: Barrier blocks style I/O terminals
(2) Single output
(3) Output wattage
(4) Universal input
(5) Output voltage
(6) Option
  C: with Coating
  N2: Screw mounting

Recommended EMI Filters

Specification

Contents Specifications
Input Voltage AC85 - 264V 1Φ *
Output Wattage 120W
Voltage/Current 48V 2.5A
Adjustable  Voltage Range 43.20 - 52.80V
Protection Circuit And Others Overcurrent Protection Works over 105% of rating and recovers automatically
Overvoltage Protection 54.00 to 67.20V
Remote ON/OFF -
Remote Sensing -
Others DC_OK LAMP
Operating Temperature/Humidity -20 to +70℃ (Required to Derating) , 20 - 90%RH (Non condensing)
Safety And Noise Regulations Agency Approvals (At only AC input) UL60950-1, C-UL (CSA60950-1) , EN60950-1, UL508, Complies with DEN-AN
Conducted Noise Complies with FCC-B, VCCI-B, CISPR22-B, EN55011-B, EN55022-B
High Attenuation Complies with IEC61000-3-2 (Class A) *
Others Dimensions (WxHxD) 38x124x117mm [1.5x4.88x4.61 inches]
Weight 580g max
Cooling Method Convection
Warranty Period 5-year (Refer to Instruction Manuals)